Option Selection
‑126‑
Struc
ture
Model
Fuse Bussmann (UL‑compliant)
Contactor Circuit Breaker
Rated Current (A)
Model
Rated Current (A) Rated Current (A)
T7
MD580‑4T112(B) 200 FWH‑200C 150 160
MD580‑4T150(B) 250 FWH‑250C 205 250
T8
MD580‑4T176(B) 275 FWH‑275C 245 250
MD580‑4T210 350 FWH‑350C 300 250
MD580‑4T253 400 FWH‑400C 410 400
T9
MD580‑4T304 500 FWH‑500C 410 400
MD580‑4T377 600 FWH‑600C 475 500
T10
MD580‑4T426‑L 700 FWH‑700C 620 630
MD580‑4T426‑L 800 FWH‑800C 620 630
T11
MD580‑4T426‑L 900 170M5015 800 630
MD580‑4T426‑L 1000 170M5016 800 800
T12
MD580‑4T650‑L 1100 170M5017 800 800
MD580‑4T725 1400 170M6017 1000 1000
MD580‑4T820 1400 170M6017 1000 1000
4.3.2 AC Input Reactor
An AC input reactor is an option used to suppress the harmonics in the input current.
In applications where strong suppression of harmonics is required, install an external
AC input reactor.
If an AC input reactor is required for models with power over 200 kW, ensure that
sufficient installation space is reserved in the cabinet for the reactor.
Models and dimensions (Inovance)
The following table lists the recommended manufacturers and models of AC input
reactors.
Figure 4‑13 AC input reactor model