Mechanical Design
‑33‑
Item
Requirement
Environment
Pollution degree: 2 or below
Install the AC drive in a place:
without direct sunlight, dust, corrosive gas, combustible or
explosive gas, oil mist, water vapor, drip, and salt.
without vibration, especially vibration caused by equipment
such as punch presses.
without foreign objects such as metal powder, oil, and
water that may enter the AC drive.
without radioactive materials, combustible materials,
hazardous gas and liquid, and salt corrosion.
providing a support made of materials other than
combustibles such as timber.
Altitude
1000 m and below: no derating.
Above 1000 m: Derate 1% for every additional 100 m.
0.75 kW to 3.7 kW models: maximum 2000 m. Consult Inovance
for use above 2000 m. 3.7kW models and above: maximum 3000
m. Consult Inovance for use above 3000 m.
Vibration resistance
Transportation with packaging: Class 2M3 requirements in
EN 60721‑3‑2
Installation without packaging: compliant with ISTA 1H
2.3.2 Clearance
T1 to T9 models
Installing one alone
Figure 2‑5 Clearance for installation of one AC drive (T1 to T9 models)