Product Information
‑21‑
Item
Technical Specifications
Customized
functions
VDC voltage
control
Load feedback energy compensates for any voltage
reduction, allowing the drive to continue to operate for a
short time.
Multi‑thread
buses
Five field buses: Modbus RTU, CANopen, PROFIBUS‑DP,
PROFINET I/O, and Modbus TCP
Multiple
encoder types
Differential encoder, open‑collector encoder, and resolver
Advanced
software tool
Software of the AC drive allows users to configure
operating parameters and
provides a virtual oscilloscope display that shows system
status.
Motor
overtempera
ture
protection
Inputs from motor temperature sensors (PT100, PT1000,
KTY‑84, and PTC‑130) are supported.
Running
Two control channels and two reference setting channels, separately
selectable
Display and
operation
on the
operating
panel
LED display The LED shows parameters.
LCD display Optional and two languages (Chinese and English)
supported
Parameter
copy
Quick parameter copy through the optional LCD
Protection
functions
Phase loss
protection
Input/output phase loss protection
Instantaneous
overcurrent
protection
The AC drive stops when the output current exceeds 250%
of the rated output current.
Overvoltage
protection
The AC drive stops when the DC voltage of the main circuit
is above 820 V.
Undervoltage
protection
The AC drive stops when the DC voltage of the main circuit
is below 350 V.
Overtempera
ture
protection
Protection triggered in case of inverter bridge
overtemperature
Overload
protection
The
P‑type AC drive stops after running at 110% of rated
current for 60s.
The G‑type AC drive stops after running at 150% of rated
current for 60s.
Overcurrent
protection
The AC drive stops when the current exceeds 2.5 times the
rated current.
Braking
protection
Braking unit overload protection Braking resistor
short‑
circuit protection
Short circuit
protection
Output phase‑to‑phase short circuit protection Output
phase‑to‑ground short circuit protection