- 53 -
2 System Commissioning
2
2.2.7 Leveling Accuracy Adjustment
There are two leveling accuracy adjustment methods, described as follows:
1. All-īoor adjustment
Parameter No. Parameter Name Setting Range Default
F4-00 Leveling adjustment 0ā60 30
F4-00 is used to adjust the car stop position at all īoors. The setting of F4-00 is effective to all īoors.
Increase F4-00 if under-leveling occurs at every īoor and decrease F4-00 if over-leveling occurs at
every īoor.
3. Single-īoor adjustment
Adjust the car stop position at each īoor separately by setting group Fr parameters.
Parameter No. Parameter Name Setting Range Default Unit Property
Fr-00 Leveling adjustment function
0: Disabled
1: Enabled
0 -
ā
Fr-01 Leveling adjustment record 1
00000ā60060
30030 mm
ā
Fr-02 Leveling adjustment record 2 30030 mm
ā
⦠ā¦
Fr-20 Leveling adjustment record 20 30030 mm
ā
The īowchart of single-īoor leveling accuracy adjustment is shown in the following īægure.