- 57 -
3 System Functions
3
Table 3-1 Parameter setting and HCB addresses of two elevators
Elevator 1 Elevator 2
Number of elevators in parallel/
group mode (F6-07)
2 2
Elevator No. (F6-08) 1 2
Actual īoor Physical īoor HCB address HCB display HCB address HCB display
B1 1 1 FE-01 = 1101
1 2 2 FE-02 = 1901 2 FE-02 = 1901
2 3 3 FE-03 = 1902
Non-stop īoor,
no hall call, but
leveling plate
required
FE-03 = 1902
3 4 4 FE-04 = 1903 4 FE-04 = 1903
4 5 No hall call No hall call 5 FE-05 = 1904
Bottom īoor
(F6-01)
1 2
Top īoor (F6-00) 4 5
Service īoor (F6-05) 65535 65531 (not stop at physical īoor 3)
3.1.2 Group Control
A GCB (MCTC-GCB-A) is additionally required to implement group control of more than two elevators.
1. A single GCB supports group control of a maximum of 4 elevators.
2. If group control of more than 4 elevators is required, two GCBs need to be installed. This scheme is
customized. For details, consult us.