6.1.4 LT/HT zone system
The central heating system can be divided into two groups,
each with a dierent heating temperature, for example a high-
temperature zone (HT) with radiators and a low-temperature
zone (LT) with underfloor heating system without its own
circulation pump.
Both zones must have their own room thermostat. LT/HR
zone control is activated by the adjustment of a number of
parameters.
There are two dierent installation sets available for installing
the LT/HT zone system:
Installation set with two-way valve (item no 093697).
Installation set with three-way valve (item no 093707).
Operational principle
The valve divides the heat over both zones. Both zones have
their own room thermostat and are alternately (time-limited)
heated through switching over the valve.
IMPORTANT
Ensure that the external pump pressure
of the central heating pump in the boiler
is taken into consideration during the
design phase of the underfloor heating.
If the radiators in the HT zone have
thermostatic radiator valves, this zone
must have a bypass valve.