9.2.7 Burner resonates
Possible causes Analysis Solution
Gas inlet pressure lower than 20mbar
or sometimes disappears.
Yes
No
The home pressure regulator may be defective. Contact the
energy company.
There is recirculation of flue gases.
Yes
No
Check the flue and air supply duct.
Gas-air control is not correctly
adjusted.
Yes
No
Check the adjustment; see §8.9 and §8.10.
Burner seal is defective. Yes
No
Replace the burner seal.
Burner is defective. Yes
Replace the burner.