64
IMPORTANT
Replace defective components
exclusively with original Intergas
components.
Not or incorrectly installing the sensors
can lead to serious damage.
Fault code Description Possible cause / solution
F007
No or insuicient
ionisation flow.
Check ionisation/ignition pin.
Check wiring of ionisation/ignition pin for breakage/shutdown.
Replace ionisation/ignition pin.
F008
Incorrect fan speed
Check fan cable.
Check and/or replace fan.
Replace burner controller.
F009
Internal fault in burner
controller.
Replace burner controller.
F010, F011
Sensor fault S0.
Check the wiring of heat exchanger sensor S0 for breakage/
shutdown.
Check whether heat exchanger sensor S0 is connected correctly.
Check for the correct operation of heat exchanger sensor S0.
Replace heat exchanger sensor S0.
F012
Sensor fault S5.
Check the wiring of flue gas sensor S5 for breakage/shutdown.
Check whether flue gas sensor S5 is connected correctly.
Check for the correct operation of flue gas sensor S5.
Replace flue gas sensor S5.
f014
Mounting fault sensor S0
Heat exchanger sensor S0 is not mounted correctly. Mount the
sensor correctly.
f015
Mounting fault sensor S1
Central heating flow sensor is not mounted correctly. Mount the
sensor correctly.
f016
Mounting fault S3
Domestic hot water sensor S3 is not mounted correctly. Mount
the sensor correctly.
F018
Flue and/or air supply
duct is blocked.
Check the flue and the air supply duct.
Clean the flue and/or the air supply duct.
F019
BMM fault.
Check BMM wiring for breakage/shutdown.
Replace BMM.
F027
Short circuit of outdoor
sensor S6.
Check the wiring of the outdoor sensor for breakage/shutdown.
Replace the outdoor sensor.
BRINK WTW connection piece is connected. Burner controller is
unsuitable for this application. Replace burner controller with the
correct version.
f028
Reset error.
Check the reset button for unintentional operation (e.g. cleaning
of control panel).
Replace burner controller.
f029
Gas valve fault.
Check the gas valve for leakage.
Replace the burner controller.
F030
Sensor fault S3.
Check wiring of domestic hot water sensor S3 for breakage/
shutdown.
Check whether domestic hot water sensor S3 is connected
correctly.
Check for the correct operation of domestic hot water sensor S3.
Replace domestic hot water sensor S3.
F031
Sensor fault S1.
Check wiring of central heating flow sensor for breakage/
shutdown.
Check whether central heating flow sensor S1 is connected
correctly.
Check for the correct operation of central heating flow sensor S1.
Replace central heating flow sensor S1.