EasyManua.ls Logo

Invertek Drives Optidrive ODP-2 - Page 76

Invertek Drives Optidrive ODP-2
76 pages
Print Icon
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
Troubleshooting
Fault
Code
No. OLED Message
Description
Corrective Action

49 Output Phase Loss One of the motor output phases is not connected to the drive.

50 Modbus Comms fault A valid Modbus telegram has not been received within the watchdog time limit set in P5-06.
Check the network master / PLC is still operating.
Check the connection cables.
Increase the value of P5-05 to a suitable level.

51 CAN Open comms trip A valid CAN open telegram has not been received within the watchdog time limit set in P5-06.
Check the network master / PLC is still operating.
Check the connection cables.
Increase the value of P5-06 to a suitable level.

52 Communications Option
Module Fault
Internal communication to the inserted Communication Option Module has been lost.
Check the module is correctly inserted.

53 IO card comms trip Internal communication to the inserted Option Module has been lost.
Check the module is correctly inserted.
Ñ82-P2MAN-IN_V3.00(Ó
82-P2MAN-IN_V3.00
Invertek Drives Ltd. Offa's Dyke Business Park, Welshpool, Powys SY21 8JF United Kingdom
Tel: +44 (0)1938 556868 Fax: +44 (0)1938 556869
www.invertekdrives.com

Related product manuals