Goodrive100-PV series solar pumping inverters Function parameters
-56-
Function
code
Name
Detailed illustration of parameters
Default
Modify
secondary winding
when applying capacitance-removing to
control the single phase motor.
0.00~100.00A
P18 Group State viewing special for solar converters
P18.00
PV reference
voltage
MPPT is implemented at the converter
side. This value is determined at the
converter side.
P18.01
Current PV
voltage
It is transferred from the boost module or
equal to the bus voltage.
P18.02
Display of MPPT
min. reference
voltage
The value displays the minimum voltage
reference during maximum power
tracking. It equals the solar cell panel
open-circuit voltage multiplied P15.26.
P18.04
Current inductive
current
It is transferred from the boost module.
This function code is valid only in AC
mode and invalid in PV mode.
P18.07
PV input power
Reserved. Unit: kW
P18.08
Previous PV input
power
Reserved
P18.09
Previous PV
voltage
Reserved
P18.10
Device
configuration
display
0x00~0x11
Ones on LED
0: PV power supply
1: AC grid power supply
Tens on LED
0: Detection indicates the system
contains the boost module.