INVT SV-DA200 AC Servo Drive PROFINET Technical Guide V2.63
41
3. Increase the ACC/DEC time
and reduce the load.
Application fault–Homing
offside
The limit switch or software
limit is enabled during
homing.
Modify the setting of P5.10 and
then execute homing after
re-power on.
Application fault–Inertia
identifying failed
1. During inertia identifying,
the motor stops rotating with
vibration of longer than 3.5s.
2. The actual ACC time for
inertia identifying is too short.
3. The inertia identifying
speed is lower than 150r/min.
1. Improve the mechanical
rigidity properly.
2. Increase the setting of P1.07.
3. Increase the setting of P1.06.