MINI and MIX Series I/O modules/Modbus
version 1.3 www.gc5.pl Page 30 / 73
Bits in register correspond to the following Analog Outputs:
No of bit in
register
No of Analog Output
0
1
1
2
2
3
3
4
4
5
5
6
Table 19 Default state of AO working as DO for MIX38 and MIX38-IP
Default state of the Analog Output 1 – 6 (4014540150)
In these 16-bits registers are stored values in mV of voltage which appear on the Analog
Outputs after power on or watchdog reset.
Configuration mode of Analog Output 1 – 6 (40168 – 40173)
These 16-bit registers contain information about the mode of the Analog Outputs according
to following table:
Register
value
0 (default)
1
2
3
4
5
Table 20 AO type settings
Hand control status of analog outputs (30015)
This register is available only for the modules with manual control of Analog Outputs.
No of bit in
register
Description
0,1
Hand status of outputs
1
2,3
Hand status of outputs
2
4,5
Hand status of outputs
3