EasyManuals Logo

Janson Controls FC100 Series User Manual

Janson Controls FC100 Series
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
10
2
CHAPTER 2 STORAGE AND INSTALLATION
2.1 Storage
The AC drive should be kept in the shipping carton before installation. In order to retain the
warranty coverage, the AC drive should be stored properly when it is not to be used for an
extended period of time.
Ambient Conditions:
Operation
Air Temperature: -10
o
C to +40
o
C (14
o
F to 104
o
F)
Atmosphere pressure: 86 to 106 kPa
Installation Site Altitude: below 1000m
Vibration: Maximum 9.86 m/s
2
(1G) at less than 20Hz
Maximum 5.88 m/s
2
(1G) at 20Hz to 50Hz
Storage
Temperature: -20
o
C to +60
o
C (-4
o
F to 140
o
F)
Relative Humidity: Less than 90%, no condensation allowed
Atmosphere pressure: 86 to 106 kPa
Transportation
Temperature: -20
o
C to +60
o
C (-4
o
F to 140
o
F)
Relative Humidity: Less than 90%, no condensation allowed
Atmosphere pressure: 86 to 106 kPa
Vibration: Maximum 9.86 m/s
2
(1G) at less than 20Hz, Maximum 5.88
m/s
2
(1G) at 20Hz to 50Hz
Pollution Degree 2: good for a factory type environment.
FC100 Series User ManualChapter 2 Storage and Installation

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Janson Controls FC100 Series and is the answer not in the manual?

Janson Controls FC100 Series Specifications

General IconGeneral
BrandJanson Controls
ModelFC100 Series
CategoryController
LanguageEnglish

Related product manuals