47
Procedure
Input
Explanation
1
K1 close
Reverse of inverter is started
2
(K1 open) press stop key
Inverter stops
3
K1 open
Running signal is removed
4
K1 close
Reverse
of inverter is started
P104 Reverse prevention setting Factory Setting: 1
SettingRange:0-1Unit:1
Explanation: 0: Reverse prohibited
1: Reverse allowed
Many devices only allow rotation in single direction. In this case, you can set the
machine in single rotation mode by this parameter. 0: Reverse prohibited
Reverse of motor is prohibited. When P104 is set at reverse prohibited, switch
between Forward and reverse is invalid.
1: Reverse allowed
Reverse of motor is enabled, switching between forward and reverse is valid.
The output frequency range of inverter is 0.1~400.00Hz. Therefore, inverter can
drive the motor higher than 50/60Hz, which could cause mechanical damage or
accident.
This parameter is to limit the inverter output frequency in order to prevent motor
operating at too higher speed.
P105 Max. frequency Factory Setting: 50.0HZ
SettingRange:0-400HZ
This parameter is to set the minimum output frequency of the inverter. If the
setting frequency is lower than the Min. frequency, inverter will output on the Min.
frequency. In some application, this function could avoid motor overheating due
to the low speed operation.
P106 Min. frequency Factory Setting: 0.00HZ
SettingRange:0-400HZ
6
Chapter 6 Description of parameter setting
FC100 Series User Manaul