55
P208 Torque boost
SettingRange:0.1~20%Unit:0.1
Factory Setting: 5%
Adjusting parameter P208 can increase voltage 3nd obtain higher torque.
Attention: Too big setting may cause motor overheating. Increase the setting
step by step until you get the requested starting torque.
P209 Rated motor voltage
SettingRange:0~380.0VUnit:0.1
Factory Setting: 380.0V
P210 Rated Motor current
SettingRange:****Unit:0.1
Factory Setting: **
P211 No load current ratio of motor
SettingRange:0~100Unit:1
Factory Setting: 40
P212 Rated motor rotation speed
SettingRange:0~6000Unit:1
Factory Setting: 1420
P213 Number of motor poles
SettingRange:0~10Unit:1
Factory Setting: 4
P214 Rated motor slip
SettingRange:0~100Unit:0.1
Factory Setting: 2.5
Please set above parameters according to the motor rating.
6
Chapter 6 Description of parameter setting
FC100 Series User Manaul