81
Setting Range:0~Max Frequency Unit:0.1
P503 — P517 are set of 15 speed of rated frequency in the running. Regarding
relationship multi speed and external terminal please refer to rated instruction
1,2,3,4 of multifunctional terminal.
Default value 100
PLC operation time 1
P518
Default value 100
P519
Default value 100
P520
Default value 100
P521
Default value 100
P522
Default value 0
P523
Default value 0
P524
Default value 0
P525
Default value 0
P526
PLC operation time 2
PLC operation time 3
PLC operation time 4
PLC operation time 5
PLC operation time 6
PLC operation time 7
PLC operation time 8
PLC operation time 9
Default value 0
P527
Default value 0
P528
Default value 0
P529
Default value 0
P530
Default value 0
P531
Default value 0
P532
PLC operation time 10
PLC operation time 11
PLC operation time 12
PLC operation time 13
PLC operation time 14
PLC operation time 15
Setting Range:0~999.9S Unit:1
PLC operation time determines internal controlling varying rated running
duration for each segment, and the running duration for each segment is
corresponding to its rate.
Default value 0
PLC operation time 15
P533
Setting Range:0~9999 Unit:1
P533 setting running direction of each segment Method of setting
running direction:
The way of setting running direction: by means of 16-bit binary system, and then
transfer to decimal system value; every bit decides the corresponding running
direction: 0 is running forward and 1 is running backward, and this parameter is
only valid when the PLC is on.
6
Chapter 6 Description of parameter setting
FC100 Series User Manaul