P202 Start frequency setting
SettingRange:0.1~10.00Unit:0.01
With regard to stop mode after stop frequency is reached, you can choose DC
injection brake and other options. If you do not choose DC injection braking, it
will stop in coasting stop mode.
1: Coasting stop
When inverter receives stop command, it will stop frequency output and it will
have free running with load until it stops.
Factory Setting: 0.5
Start frequency is the initial frequency when inverter starts. For device with
heavy load or requires large starting torque, increasing start frequency can make
start easier. However, if the start frequency is too high, it may cause over current
protection.
P203 Stop frequency setting
SettingRange:0.1~10.00Unit:0.1
Factory Setting: 0.5HZ
Stop frequency setting
When inverter receives stop command, it reduce the output frequency until the
stop frequency, then it will start coasting stop or DC injection brake stop
according to the setting.