74
Default value 0.0
Automatic energy-saving selection
P413
Setting Range:0~100 Unit:1
P413 Automatic energy-saving selection
In constant-speed running of automatic energy-saving selection, best voltage
value may be calculated by loading condition and provided to load, in order to
achieve best energy-saving.
Attention: for running that load changes frequently or is almost at full load, this
function is not suitable.
F
Default value 0.0
Restart after instant power off
P416
Setting Range:0~1 Unit:1
Explanation: 0: Invalid: no restart after instant power failure
1: Valid: frequency tracing start-up
0: Invalid
Inverter clears the running command after power failure. After power is
recovered, inverter will not start automatically.
1: Frequency tracing enable
When power is shut-off in short time, inverter keeps the running command as
effective. When power is recovered in time, inverter will tracing the motor speed
and resume output.
Attention: when instant power failure restarting is enabled, inverter may start
the motor automatically. Please take care of the safety when use this function.
6
Chapter 6 Description of parameter setting
FC100 Series User Manaul

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Janson Controls FC100 Series and is the answer not in the manual?

Janson Controls FC100 Series Specifications

General IconGeneral
BrandJanson Controls
ModelFC100 Series
CategoryController
LanguageEnglish

Related product manuals