80
Default value 0
PLC running mode
P502
Setting Range:0~4 Unit:1
Explanation:
0: PLC stop running after a week
1: PLC pause mode, stop running after a week
2: PLC cycle running
3: Cycle running of PLC pause mode
4: After running for a week, PLC continues running by the end of running
frequency
PLC running mode determines rnnning status of internal multispeed, either
running one circle or cycle running. P502 is only valid when PLC starts up.
PLC pause mode means that when completing every speed in the running
process of internal multi-speed, the speed will be down, stop, and accelerate to
the next speed. The illustration is as below:
Frequency
Users may select proper running mode according to actual conditions.
Default value 10.0
Multi-speed 1
P503
Default value 15.0
P504
Default value 20
P505
Default value 25.0
P506
Default value 30.0
P507
Default value 35.0
P508
Default value 40.0
P509
Default value 45.0
P510
Default value 50.0
P511
Multi-speed 2
Multi-speed 3
Multi-speed 4
Multi-speed 5
Multi-speed 6
Multi-speed 7
Multi-speed 8
Multi-speed 9
.0
Default value 10.0
P512
Default value 10.0
P513
Default value 10.0
P514
Default value 10.0
P515
Default value 10.0
P516
Default value 10.0
P517
Multi-speed 10
Multi-speed 11
Multi-speed 12
Multi-speed 13
Multi-speed 14
Multi-speed 15
6
Chapter 6 Description of parameter setting
FC100 Series User Manaul