Parameter P409 is the torque limit level during acceleration. When output
current reaches the setting value, inverter will stop accelerating, and when
current is below the set value, inverter resume the accelerating.
100% current is the rated current of inverter, when P409 is set to be 0, then
accelerating torque limit is invalid, and it does not have protecting function.
Default value 00
Constant-speed torque limiting level
P410
Setting Range:0~200 Unit:1
Parameter P409 is the torque limit level during constant speed. When output
current reaches the setting value, inverter automatically reduce the output
frequency in order to reduce the load. When the output current drops, inverter
increase output frequency to the setting (100% current is rated current of
inverter).
When P410 is set to be 0, constant-speed torque limiting level is invalid and
cannot protect.
Default value 1
Deceleration over-voltage prevention selection
P410
Setting Range:0~1 Unit:1