The specified flow rate relates to the maximum available heat capacity.
If required, enter your individual values in the prepared table.
Consult KAESER SERVICE if you wish to use a different heat-receiving medium.
The primary side of the heat exchanger is connected to the cooling oil circuit of the machine.
The specifications refer to the secondary side of the heat exchanger.
Individual design data
My value
Heating from [°C]
Heating to [°C]
Temperature difference
(ΔT) [K]
Maximum available heat
output [kW]
(relative to ___ bar work‐
ing pressure)
Flow rate [m
3
/h]
Pressure drop [bar]
Tab. 34 Heat recovery: Individual design data
Component sprecification:
Feature Value
Material 1.4401
Braze Copper (Cu)
Max. working pres‐
sure [bar]
10
Minimum permissible in‐
let temperature [°C]
5
Max. permissible inlet
temperature* [°C]
45
Continuously possible
outlet temperature [°C]
70
Maximum permissible
outlet temperature [°C]
(Component limit value)
100
Maximum permissible
flow rate [m
3
/h]
8.7
Unsuitable cooling media Salt water
Consult KAESER on the suitability of water.
* Consult KAESER about higher values.
Tab. 35 Specification: Heat exchanger (Option W2/W3)
2 Technical Specifications
2.15 Heat recovery
901824 12 E
Operating Manual Screw Compressor
ASK
15

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER ASK Series and is the answer not in the manual?

KAESER ASK Series Specifications

General IconGeneral
ModelASK Series
TypeRotary Screw Compressor
Motor TypeIE3 Premium Efficiency
CoolingAir / Water
DriveDirect
Control SystemSIGMA CONTROL
WeightVaries by model