Heat capacity
Maximum heat capacity
available*
BSD 40 BSD 50 BSD 60
[kW] 27.0 33.3 40.8
[MJ/h] 97 120 147
[kcal/h] 23216 28616 35082
* With the combination valve set to open at 176 °F.
Tab. 31 Heat capacity (option W2/W3)
Flow rate for heating from 113 °F to 158 °F (equivalent to ΔT = 45F)
BSD 40 BSD 50 BSD 60
Flow rate [gpm] 4.0 5.3 6.2
Pressure drop [psi] <2.9 <3.6 <3.6
Tab. 32 Flow rate / pressure loss (option W2)
Flow rate for heating from 59 °F to 158 °F (equivalent to ΔT = 99F)
BSD 40 BSD 50 BSD 60
Flow rate [gpm] 1.8 2.2 2.6
Pressure drop [psig] <1.5 <2.2 <2.2
Tab. 33 Flow rate / pressure loss (option W3)
2 Technical Data
2.16 Heat recovery
9_5708 08 USE
Service Manual Screw Compressor
BSD
15
Option W2
Option W3