Parameter sets
© KEB, 2008-02 COMBIVERT R6-S Page3.7 - 9
3
10
Input-coded set source
with input-coded set source
- maximally 7 of the internal or external inputs may be programmed to set source (0...7 sets), in order to avoid
set source errors.
- the lowest of the selected inputs has priority at Fr.02 = „3"
(ST>RST>R>F>I1>I2>I3>I4>IA>IB>IC>ID)
- the highest of the selected inputs has priority at Fr.02 = „4“
(ID>IC>IB>IA>I4>I3>I2>I1>R>F>RST>ST)
Example2:set0...5shallbeselected with 5 inputs (I1, I2, I3, IB and ID)
1.) Set parameter Fr.07 to value „2672“
2.) Set Fr.02 to value „3“ (set source input-coded via terminal strip)
Id IB I3 I2 I1 Set Set
0
1
2
3
4
5
I1
I2
I3
IB
ID
Set
Set
Set
Set
Set
Set
Fr.02 = 3 4
0 0 0 0 0 0 0
0 0 0 0 1 1 1
0 0 0 2 0 2 2
0 0 3 0 0 3 3
0 4 0 0 0 4 4
5 0 0 0 0 5 5
5 0 3 0 0 3 5
5 0 3 0 1 1 5
Reset to set 0 / input selection (Fr.11)
Parameter Fr.11denesaninput,independent of the actual parameter set it can be switched in parameter set
0. This function is only active at Fr.02 = 2...4
- at static input assignment the inverter remains in set 0, as long as the input is set.
- atslope-triggeredinputsset0isactivatedwiththerstslope.Withthesecondslopetheactivatedpa-
rameter set by the other inputs is selected again.