PEGAsys™ LV
The total SLC wiring resistance (24.1 ) when using #16 AWG wire is less than the maximum SLC wiring resistance of
26 . The SLC wiring resistance using #16 AWG wire is acceptable.
If we select Coleman Cable wire, P/N 98161 (from Recommended Wire Listing), the total SLC wiring capacitance is:
3,000 ft x 20 x 10
-12
farads/ft. = .06 x 10
-6
farads (or, 0.06 µF).
Coleman Cable wire, P/N 98161, is acceptable.