PAS SERIES Setup 1-5
1000W type
The AC power cord that is included with the 1000W type can be used
on either a 100-VAC or 200-VAC system.
Risk of electric shock.
Before you connect the power cord, turn off the
switchboard breaker (a switch that cuts off the power
supply from the switchboard).
The PAS series is an IEC Safety Class I equipment
(e
quipme
nt with a protective conductor terminal). Be
sure to ground the product to prevent electric shock.
Connect the ground terminal to earth ground.
Be sure to have a qualified engineer connect the
po
we
r cable to the switchboard.
The switchboard breaker must meet the requirements
sho
wn belo
w.
Inside the power supply, an appropriate protective cir-
cuit is connected to the input terminal. Be sure to
connect th
e wires correctly by matching the U, V, W,
and (GND) between the switchboard and the PAS
series.
Use the supplied power cord to connect to the AC line.
In an emergency, turn off the switchboard breaker to disconnect the
PAS series from the AC power line.
The PAS series is a piece of equipment that conforms to IEC Over-
voltage Category II (equipment that consumes energy supplied from a
fixed installation).
Switchboard breaker requirements
Rated current: 20 A (100 V system)/ 10 A (200 V system)
For safety, breakers whose rated current exceeds the specified cur-
rent cannot be used.
Only use the breaker with the PAS series.
Keep the breaker readily accessible at all times.
Indicate that the breaker is dedicated
fo
r use with the PAS series
and that it is used to disconnect the product from the AC power line.
WARNING
CAUTION