2)Host computer can only access function code of Group U0 after decryption(write correct factory password into
U0.00).If there is no communication for 5 minutes after acquiring access right,the right will disable automatically,and
it need to enter password again to access Group U0.
3)After acquiring the access right of Group U0,if host computer read U0.00,it will return 0000 instead of actual
factory password.
4)The operation of host computer and keypad to user password is independent. They need to enter the correct
password separately to acquire the access right.
5)Host computer has no right to modify factory password.When host computer write data into U0.00, it will
return invalid operation unless the data is correct password.
2. Application example
SV100 only support 16bit access.
Start No.5 VFD to perform forward rotation.
No.5 VFD stops in mode 0.
No.5 VFD jogs forward.
No.5 VFD stop jogging.
No.5 VFD reset fault:
Read the operating frequency of No.5 VFD and the response operating frequency of the VFD is 50.00Hz:
Number of
registers or
bytes
Rewrite the acceleration time 1(Function code A0.06) of No.5 VFD to 10.0s and can’t save after power failure.