A8.01 Fault masking selection 1
A8.02 Fault masking selection 2
Please set the fault masking selection
function carefully,or it may cause worse accident,bodily
injury and property damage.
A8.03 Motor overload protection
mode selection
0: Disabled
The overload protection is disabled. Be careful to use
this function because the drive will not protect the motor
when overload occurs.
1:Common motor (with low speed compensation)
Since the cooling effects of common motor deteriorates
at low speed (below 30Hz), the motor’s overheat
protecting threshold should be lowered, which is called
low speed compensation.
2: Variable frequency motor (without low speed
compensation)
The cooling effects of variable frequency motor is not
affected by the motor’s speed, so low speed
compensation is not necessary.
Auto reset function can reset the fault in preset times and
interval. When A8.04 is set to 0, it means ―auto reset‖ is
disabled and the protective device will be activated in
case of fault.
Note:
The IGBT protection (E010) and external equipment
fault (E015) cannot be reset automatically.
A8.06 Fault locking
function selection.
0:Disable.
1:Enable.
6.10 Group b0
0.4~999.9kW【dependent on
drive’s model】
0~rated volotage of drive
【 dependent on drive’s
model】
0.1~999.9A【dependent on
drive’s model】
1.00~ 300.00Hz【 dependent
on drive’s model】
b0.04 Number of
polarities of motor
These parameters are used to set the motor’s parameters.