99
The Filters function is based on time measurement, lters physical condition is not analyzed
Filtry ->
Filters – activation/deactivation of alarm function of the contaminated lter Months –
setting of lter replacement frequency (1-6 months)
Date – read and set current date
Replace lters in – readout of days left to lter replacement
11.4.7 Additional functions
selected Additional functions (the are visible after activa-
tion of the corresponding settings in the „Service settings”
menu)
Tabela Nr 17
UV lamp ->
Running time – readout of the current running time of the system
Enter operating time – possibility of entering the running time
Set counter – entering / resetting to the set running time
A_UV_LampTime – Activation of the alarm, indicating exceeding of the UV lamps
running time
Limit – UV lamps running time limit setting
ES lter ->
Sensor type – possibility to select PM2,5, PM10 air quality sensor Fan control – the
possibility to activate air quality control with fans
Kp – icrease of the air quality control system
Ti – Integration constant of the air quality control system
Control system limit – maximum control value of the air quality controller
PM2.5 – sensor concentration setting PM2.5
PM10 – sensor concentration setting PM10
Min. supply – minimum eciency of the supply fans at maximum PM concentration
Min. exhaust – minimum eciency of the exhaust fans at maximum PM concentration
Sensor range – signal scale conguration 0-10VDC air quality sensor
Humidity
sensor ->
Max humidity – humidity limit of exhausted air above which the system switchesto
operating mode with max output
0V – scaling the humidity sensor for 0VDC voltage
10V – scaling the humidity sensor for 10VDC voltage
Measurement – current measured humidity value
CO2 sensor
Max CO2 – CO2 limit of exhausted air above which the system switches to operating
mode with max output
0V – scaling the CO2 sensor for 0VDC voltage 10V – scaling CO2 sensor for 10VDC
voltage Measurement – current measured CO2 value
Airow
regulation
Measurement pressure – measurement from pressure sensor
Sensor range – sensor measurement range setting Supply – setting of a min and max
air supply output Exhaust – setting of min and max air exhaust output