EasyManua.ls Logo

Klimor EVO-T Plus - Communication. Modbus with the Bms System; Modbus Variables. Rs485-1; Variable Representation

Default Icon
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
105
12. MODBUS VARIABLES. RS4851 COMMUNI
CATION. MODBUS WITH THE BMS SYSTEM
The controller has implementations of Modbus RTU proto-
col. In order to perform network coupling it is necessary to
connect RS-485 buses to the RS485-1 port on the controller
bar. The modbus address is set in the programming device
menu (MAC address, see point 12).
Default communication parameters:
transmission rate of 9600 bps (can be changed from the
built-in or external HMI)
8 bits of frame
2 stop bits
Lack of parity
All variables are 32-bit Holding Register-type values Mod
-
bus registers are 16-bit coded and that is why one 32-bit
variable takes two 16-bit variables. Use Modbus 0x03 com-
mand to read variables, 0x06 to write 16-bit single variable
and 0x10 to write many variables.
12.1 Variable representation
The table below shows all variables of the control system.
The variables have go several number representations:
Multistate – specied integral values of variable corre-
spond to described conditions
Decimal – 32-bit variable value is considered as a integer
type with a symbol
Fixed – a xed type in which the 8 least signicant bits
are intended for a fractional part, while the remaining 24
bits are the total part with a symbol.
Therefore, the accuracy of Fixed value is 1/256. To scale the
value represented by Fixed to the target (proper) value,
multiply it by 1/256 = 0.00390625.

Table of Contents

Related product manuals