5.1 System operation principle:
When the system is switched on, the supply and exhaust
fans are activated with minimum output for the by-pass
closing time. The fans are controlled in a stepless manner,
each of them with a separate independent signal. For about
3 min. the algorithm works with the supply air sensor as the
leading sensor, only after this time it returns to the master
sensor selected by the user.
Depending on cooling/heating demand the system au-
tomatically turns on the electrical heater, then the water
heater or water/DX cooler (if installed). The electrical heat-
er and the valve of water heater/cooler are controlled in
a stepless manner. The freon cooler solenoid valve is con-
trolled by an on/o signal.
Turning on the cooler and heaters occurs only within the
temperature ranges dened in the menu
//REG. TEMP, described in the chapter: Control of the com-
pact EVO-T +.
Anti-frost protection of the cross counterow/rotary heat
exchanger is based on an appropriate algorithm of the unit
operation – it turns on when the temperature indicated by
B4 sensor drops below preset value in the Tzad.rec param-
eter. Once the frost is eliminated the system switches back
to the previous operation mode
Thermal protection of the electric heater:
- TK thermostat which TURNS OFF the electric heater once
the temperature exceeds the preset value (+70°C). As soon
as temperature drops down, the electric heater turns on
automatically. If the thermostat is activated THREE TIMES,
the EVO-T+ is TURNED OFF. RESTARTING the device – after
manual alarm reset at the control box.
- Once the EVO-T+ is turned o, the electrical heater is im-
mediately turned o and the fans are turned o after 120
seconds (the heater is being cooled down in order to pre-
vent activation of the TK thermostat)
Thermal protection of the water heater from freezing
through:
- antifreeze thermostat with a capillary which, when the
temperature behind the exchanger falls below the set
value (+5°C), turns the system OFF and controls 100% of
the valve and switches on the circulation pump. When the
temperature rises and the min. warm-up time elapses, the
system automatically returns to normal operation. If the
thermostat is activated THREE TIMES, the EVOT+ is TURNED
OFF. RESTARTING the device – after manual alarm reset at
the control box..
The control system is prepared for controlling the ground
heat exchanger (GHEX) damper or the pre-heater. In winter
the GHEX heats up the intake air while in summer – cools it
down. Alternatively, it is possible to control a preeliminary
electric heater, to which only the PWM control signal and
the operating permit are given. The power supply and pro-
tection of the preeliminary heater remains with the user.
It is possible to purchase a dedicated control unit for the
three-phase electric preheater.
The system is also prepared for controlling the heater and
the secondary water cooler with 0÷10V signal. You can also
provide ON/OFF signal to the solenoid valve of the direct
expansion cooler – the valve is not provided. As far as the
cooperation with the circulation pump M1 of the water
heater is concerned, the unit’s automatics issues a poten-
tial-free signal for the control, while the provision of power
to the pump is left to the user.
In order to improve the heating eciency the system fea-
tures the fan output reduction algorithm. The algorithm
will be applied if the supply air duct temperature is main-
tained for more than 5 minutes below the lower supply
temperature limit (Tlo parameter – see
Temperature adjustment” menu description). The fan out-
put will be getting down to 50% of the nominal preset,
however it will not get lower than the factory preset actua-
tion (factory default: 30%).
In emergency situation it is possible to turn o the system
with signal provided at DI2 input of the controller. Closed
contact
– normal operation, open – switching o the device. Re-
move the jumper in order to use this input – see the wiring
diagram.
Optionally, you can control shut-o damper actuators on
supply and exhaust. Depending on the conguration, se-
lect one of the digital outputs RE1(PK1)-RE5(PK5) and as-
sign the function Operation signal.
NOTE!
If the pre-heater or GHEX is used, the B3 external tem
-
perature sensor should be removed from the unit and
installed (cable extension required) BEFORE the air inlet
to the GHEX.
If the additional water cooler or heater is used, the B1
air inlet temperature sensor should be installed (cable
extension may be required) DOWNSTREAM the heat
exchanger.
It is not recommended to reduce the fan speed below
50% due to the possibility of overheating of the electric
heater, which requires manual reset of the thermostat.
See other into in chapter: Control of the compact
EVO-T+ AHU.