73
2.4 Technical parameters
Table 1 Technical parameters EVO-T+8000
PARAMETERS EVO-T + 8000 CPR EVO-T + 8000 RR
Nominal air ow rate [m
3
/h] at External static pressure 800/170 Pa 800/80 Pa
Unit dimensions
L
[mm]
1860 1635
L1 919 807
B 1012
B1 1048
H 355
H1 395
Net weight [kg] / Gross weight with pallet 135 / 165 115/150
Flexible duct connections 465 x 290
Power supply voltage: 230 V; 50 Hz
Heat exchanger counterow rotary
Heat exchanger eciency* up to 91% up to 80%
Exchanger motor
Power
N/A
25 W
Voltage 230 V; 50 Hz
Absorbed current 0,23 A
Air temperature -25 do 50°C
Fans
Power 2×200 W
Voltage 230 V; 50 Hz
Absorbed current 2×1,2 A
Air temperature -25 do 50°C
Acoustic power level
To room at capacity
30% 33 dB(A) 33 dB(A)
100% 52 dB(A) 52 dB(A)
Into the duct at capacity
30% 54dB / 49dB(A) 54dB / 49dB(A)
100% 60dB / 57dB(A) 60dB / 57dB(A)
Control system Digital controller
Exhaust and outlet air lter according to EN 779 / according to EN ISO 16890
G4 / Coarse 80% – standard
M5 / ePM
10
50% – option
F7 / ePM
1
60% – option for air supply
EH heater on supply air inlet after heat recovery exchanger (option WH/EH) 3600 W
*Note: Data provided by manufacturers of counterow plate heat exchangers, according to the EN 308 and EUROVENT