EasyManua.ls Logo

Klimor EVO-T Plus - Page 103

Default Icon
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
101
11.5.1 ALARMS LIST
Table 21
ALARMS Alarm type System response, procedure
Digital inputs
A_ThHE, A_3xTh
-
HE
Fading Blocking
Thermal protection of preliminary and/or secondary heater. The signal from
electric heater overheating thermostat or from electric heater alarm connector is
provided to this input:
Normal state – heater temperature is low, there is 24VAC signal on the digital
input
Alarm condition – heater temperature is too high, no 24VAC signal on the digital
input
Response to the alarm condition: the system operates without the heater until
overheating is eliminated, once overheating is eliminated the alarm disappears
and the system operates with the heater, if the A_ThHE alarm is triggered 3 times
within 1 hour, the system is stopped and the A_3xThHE alarm is displays, which
has to be conrmed.
Digital input Din1
A_ThHWair,
A_3xThHWair
Fading Blocking
Protection of the heater against freezing with an anti-freeze thermostat.
Normal state – temperature behind the heater is higher than set – on the ther-
mostat, there is a 24VAC signal on the digital input
Alarm condition – the temperature behind the heater is lower than set on the
thermostat, there is no 24VAC signal on the digital input Reaction to the alarm
condition: STOP system, heater 100% until the thermostat is heated up, after the
thermostat is heated up and there is no low thermostat temperature the system
returns to operation, after 3 times within an hour alarm A_ThHWair occurs, sys-
tem operation stops and alarm A_3xThHWair is displayed requiring conrmation.
Digital input Din6
A_AF Disappearing
Cooperation with re protection unit
Normal state – no re, there is 24VAC signal on the digital input Alarm state
re is present, there is no 24VAC signal on the digital input
Reaction to the alarm state: STOP system until the re disappears, after the
re is extinguished, the system automatically returns to the operating state
equipment alarm
Digital input Din3
A_SupFilterES Disappearing
Testing of the pollution level of the intake ne lters
with a pressure with the automation the lters:
Normal state – dirt level is acceptable, pressure dierence before and behind
the lter is below the preset value, there is no 24VAC signal on the digital input.
Alarm state – dirt level is unacceptable, the pressure dierence before and
behind the lter is above the preset pressure switch, there is a 24VAC signal on
the digital input
Reaction to the alarm state: the system is working, an alarm of a dirty lter is
displayed,
In case of such an alarm it is necessary to replace the lter with a new one
immediately, working with a dirty lter lowers the AHU’s airow and may cause
the lter to break, which in turn may cause dirt and damage to heat/cooling
exchangers due to the customer’s fault.
Input depending on selection in the advanced settings menu

Table of Contents

Related product manuals