EasyManuals Logo

Kohler KEP User Manual

Kohler KEP
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
TP-6745 7/10 39Section 2 Troubleshooting
MPAC 1500
controller display is
blank.
Are any LEDs on the
controller illuminated?
Verify power directly
on circuit board P1-12 and
P1-4 (Normal), and P1-6 and
P1-7 (Emergency).
Inspect the
ribbon cable. Is the ribbon
cable connected incorrectly?
Unplug the ribbon cable and reconnect it
correctly.
Replace the display assembly, which
includes attached ribbon cable.
NO
YES
YES
NO
NO
NO
YES
Replace the Main Logic Board (MLB).
Trace leads back to the
contactor and sensing
terminals. Refer to the wiring
diagrams provided with the
transfer switch. Repair or
replace damaged leads or
harness.
NO
Poor pin connection or
broken wire at P1. Correct
the pin or wire connection.
YES
Check for display operation.
Does the display operate?
Is the ribbon cable
damaged?
NO
YES
Note: To prevent damage to the controller and the device, NEVER
remove or reapply devices while the controller is energized. Follow
the safety precautions during this troubleshooting procedure.
Complete.
Verify power to the ATS.
Check AC line voltage at P1-12(A)
and P1-4(C) for the normal source.
Check AC line voltage at P1-7(A)
and P1-6(C) for the emergency
source. Line voltage found
at all points?
YES
SB-697
Figure 2-20 Blank Display Troubleshooting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler KEP and is the answer not in the manual?

Kohler KEP Specifications

General IconGeneral
BrandKohler
ModelKEP
CategorySwitch
LanguageEnglish

Related product manuals