Table 17. Electrical Output (All Models)
(voltage configurable or
auto-sensing)
Output Overload
(Normal Mode)
108%±5%–150%±5%: Load transfers to Fault mode after
30 seconds.
150%±5%–200%±5%: Load transfers to Fault mode after
300 ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
Output Overload
(Bypass Mode)
100%±5%–130%±5%: Load transfers to Fault mode after
20 minutes.
130%±5%–150%±5%: Load transfers to Fault mode after
2 minutes.
150%±5%–200%±5%: Load transfers to Fault mode after
15 seconds.
>200%±5%: Load transfers to Fault mode after 140 ms.
Output Overload
(Battery Mode)
108%±5%–150%±5%: Load transfers to Fault mode after
30 seconds.
150%±5%–200%±5%: Load transfers to Fault mode after
300 ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
<3% THD on linear load; <5% THD on non-linear load
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of
utility)