Table 18. Electrical Output Connections (0TAll0T Models)
Model
Output Connections
Output Cables
1K-0T RT
(IEC C13-10A)*6
IEC320 C14-10A
1.5K-0T RT
(IEC C13-10A)*6
IEC320 C14-10A
2K-0T RT
(IEC C13-10A)*6
(IEC C19-16A)*1
IEC320 C14-10A
IEC320 C20-10A
3K-0T RT
(IEC C13-10A)*6
(IEC C19-16A)*1
IEC320 C14-10A
IEC320 C20-10A
Table 19. Environmental and Safety (All Models)
208/230/240 Vac Models
Surge
Suppression
EN 61000-2-2
EN 61000-4-2, Level 4
EN 61000-4-3, Level 3
EN 61000-4-4, Level 4 (also on signal ports)
EN 6100-4-5, Level 4 Criteria A
EMC
Certifications
CE per IEC/EN 62040-2,
Class B
Class B
EMC
(Emissions)
IEC 62040-2:ed2:2005 / EN 62040-2:2006
Safety
Conformance
IEC 62040-1-1, IEC 60950-1
Agency
Markings
CE
Operating
Temperature
0°C to 40°C (32°F to 104°F) in Online mode, with linear
derating for altitude
NOTE Thermal protection switches load to Bypass in case of
overheating.
Storage
Temperature
-20°C to 40°C (-4°F to 104°F) with batteries
-25°C to 55°C (-13°F to 131°F) without batteries
Transit
Temperature
-25°C to 55°C (-13°F to 131°F)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KStar MEMO PLUS RT II (MP9100RTII-0.9) 1-3K and is the answer not in the manual?

KStar MEMO PLUS RT II (MP9100RTII-0.9) 1-3K Specifications

General IconGeneral
BrandKStar
ModelMEMO PLUS RT II (MP9100RTII-0.9) 1-3K
CategoryUPS
LanguageEnglish

Related product manuals