Up to 3,000 meters (9,843 ft) above sea level
Up to 10,000 meters (32,808 ft) above sea level
<55 dBA at 1 meter typical
Table 20. Battery Runtimes (in Minutes) at 100% Load (ALL Models)
NOTE Battery times are approximate and vary depending on the load
configuration and battery charge.
1000 VA: 24 Vdc (2, 12V, 9 Ah)
1500 VA: 36 Vdc (3, 12V,9 Ah)
2000 VA: 48Vdc (4,12V,9Ah)
3000 VA: 72 Vdc (6 , 12V,9Ah)
1K -EBP: 24 Vdc (2 x 2 ,12V, 9 Ah)
1.5K -EBP: 36 Vdc (2 x 3 ,12V, 9 Ah)
2K -EBP: 48Vdc (2 x 4 ,12V, 9 Ah)
3K -EBP: 72 Vdc (2 x 6 ,12V, 9 Ah)
(4) 30A/250 Vdc fuses per EBP
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year
float service life at 25°C (77°F)
Advanced monitoring for earlier failure detection and warning
Internal batteries: 3 hours 1 EBP: 9 hours; 2 EBPs: 15 hours; 3 EBPs: 21 hours;
4 EBPs: 27 hours
External six-pole Anderson connector on UPS for connection to EBP