EasyManua.ls Logo

Kuka KR C4 compact - Page 60

Kuka KR C4 compact
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
60 / 93 Issued: 20.04.2018 Version: Spez KR C4 compact V10
KR C4 compact
Test outputs A and B are fed with the supply voltage of the CIB_SR. Test out-
puts A and B are sustained short-circuit proof. The test outputs must only be
used to supply the CIB_SR inputs, and for no other purpose.
The wiring example can be used to achieve compliance with SIL2 (DIN EN
62061) and Cat. 3 (DIN EN 13849).
Dynamic testing
The switch-off capability of the inputs is tested cyclically. For this, the test
outputs TA_A and TA_B are switched off alternately.
The switch-off pulse length is defined for the CIB_SRs as t1 = 625 μs (125
μs – 2.375 ms).
The duration t2 between two switch-off pulses on one channel is 106 ms.
The input channel SIN_x_A must be supplied by the test signal TA_A. The
input channel SIN_x_B must be supplied by the test signal TA_B. No other
power supply is permissible.
It is only permitted to connect sensors which allow the connection of test
signals and which provide floating contacts.
The signals TA_A and TA_B must not be significantly delayed by the
switching element.
Switch-off pulse
diagram
1 Failsafe input CIB_SR
2CIB_SR
3 Robot controller
4 Interface X11
5 Test output channel B
6 Test output channel A
7 Input X, channel A
8 Input X, channel B
9 System side
10 Floating contact
Fig. 6-6: Switch-off pulse diagram, test outputs
t1 Switch-off pulse length
t2 Switch-off period per channel (106 ms)
t3 Offset between switch-off pulses of both channels (53 ms)
TA/A Test output channel A
TA/B Test output channel B
SIN_X_A Input X, channel A
SIN_X_B Input X, channel B

Table of Contents

Related product manuals