Device
Working tem-
perature range
without a heater
Working tem-
perature range with
a heater
Temperature sta-
bility
1
Dimensions
(W x D x H)
Weight
VC 10000 -20 – 40 -20 – 80
±0.1
650 x 670 x 1250 147
VC 10000 W -20 – 40 -20 – 80
±0.1
650 x 670 x 1250 140
1
the temperature stability is load-dependent in devices without a heater
Ä “Cooling in a device without a heater and in the [autom.] setting”
on page 45
The housing is 140 mm higher in the devices VC 1200 (W) and
VC 2000 (W), which have a more powerful pump.
Table 14: Air-cooled devices
Device
Free space around the
device
Exhaust air (air-cooled
devices)
cm (front/back/right/left) m³/h
VC 1200 20/20/20/20 650
VC 2000 20/20/20/20 650
VC 3000 50/50/20/20 1300
VC 5000 50/50/20/20 2500
VC 7000 50/50/20/20 4500
VC 10000 50/50/20/20 4500
Table 15: Water-cooled devices
Device Free space around the device
cm (front/back/right/left)
VC 1200 W 20/20/0/0
VC 2000 W 20/20/0/0
VC 3000 W 20/20/0/0
VC 5000 W 20/20/0/0
VC 7000 W 20/20/0/0
VC 10000 W 20/20/0/0
Free space around the device
V08 Variocool 83 / 97