10 Parameter reference
10.2 Parameter list | C00137
255
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00137
C00141
Parameter | Name:
C00137 | Device state
Data type: UNSIGNED_16
Index: 24438
d
= 5F76
h
Display of the current device state
Selection list (read only)
0 Reserved
1 Init
2 MotorIdent
3 ReadyToSwitchON
4 SwitchedON
5 OperationEnable
6 Reserved
7 Trouble
8 Fault
9 Reserved
10 SafeTorqueOff
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00141 | Device settings
Data type: UNSIGNED_8
Index: 24434
d
= 5F72
h
As of version 03.00.00
Selection list
0Inactive
1Active
Subcodes Lenze setting Info
C00141/1 0: Inactive Always save parameters
When this function is activated, every parameter
change is saved in the memory module. A manual sa-
ving of parameter sets is not required anymore.
Note:
Activating this function is not permissible if parameters
are changed very frequently (e.g. in case of cyclic writing
of parameters via a bus system).
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1