7 Drive application
7.3 Setting parameters (short overview)
139
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.5 Terminal assignment of the control modes
The following table shows which functions are assigned to the digital terminals in the different control modes.
Related topics:
User-defined terminal assignment
( 114)
Pre-assignment of the drive application
( 133)
Analog input Assignment of the digital terminals Relay output
Control mode A1U DI1 DI2 DI3 DI4 DO1 NO / COM
Terminals 0
Setpoint selection
10 V ≡ 100 % refe-
rence speed (C011
)
JOG 1/3 JOG 2/3 DCB Cw/Ccw Status
"Drive is ready to
start"
Status
"An error occurred"
Terminals 2
JOG 1/3 JOG 2/3 QSP Cw/Ccw
Terminals 11
Cw/Ccw DCB MPotUp MPotDown
Terminals 16
JOG 1/3 JOG 2/3 Cw/QSP Ccw/QSP
Keypad
- ----
PC
- ----
CAN
-QSP---
Abbreviations used:
JOG Selection of the fixed setpoints 1 ... 3 in C039/1...3
DCB Manual DC-injection braking
Cw/Ccw CW/CCW rotation
QSP Quick stop
MPotUp Motor potentiometer: Increase speed
MPotDown Motor potentiometer: Decrease speed
Cw/QSP Fail-safe selection of the direction of rotation in connection with quick stop
Ccw/QSP