4 Device control (DCTRL)
4.1 Device commands
48
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.1.1 Load Lenze setting
The C002/1 = "1: : On / start" device command resets the parameters to the Lenze setting which are
saved in the controller firmware.
Can only be executed if the controller is inhibited; otherwise, the feedback C002/1
="6: No ac-
cess - controller inhibit" will be returned.
All parameter changes which have been carried out after the last time the parameter settings
were saved will be lost!
This device command has an effect on the settings of the parameters of the operating system,
application and module.
How to load the Lenze setting:
1. If the controller is enabled, it must be inhibited, e.g. by executing the "Enable/Inhibit cont-
roller" device command" (C002/16
="0:Off / ready").
2. Execute the "Load Lenze setting" device command
C002/1
="1:On / start"
The load process may take a couple of seconds. After the device command has been called
in C002/1
a dynamic status information ("Work in progress" "Off / ready") is returned.
4.1.2 Loading parameter settings
The C002/2 = "1: On / start" device command reloads all parameters from the memory module to
the controller.
Can only be executed if the controller is inhibited; otherwise, the feedback C002/2
="6: No ac-
cess - controller inhibit" will be returned.
All parameter changes which have been carried out after the last time the parameter settings
were saved will be lost!
This device command has an effect on the settings of the parameters of the operating system,
application and module.
How to reload the starting parameter settings from the memory module:
1. If the controller is enabled, it must be inhibited, e.g. by executing the "Enable/Inhibit cont-
roller" device command (C002/16
="0:Off / ready").
2. Execute the "Load Lenze setting" device command:
C002/2
="1:On / start"
The load process may take a couple of seconds. After the device command has been called
in C002/2
2 a dynamic status information ("Work in progress" "Off / ready") is returned.
Note!
When the device is switched on, all parameters are automatically loaded from the me-
mory module to the main memory of the controller.