9 System bus "CAN on board"
9.1 General information
172
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.1.3 Communication time
The communication time is the time between the start of a request and the arrival of the correspon-
ding response.
Tip!
The communication times in the CAN network depend on:
the processing time in the device
the telegram runtime (baud rate/telegram length)
the bus load (especially if the bus is charged with PDOs and SDOs at a low baud rate)
Processing time in the 8400 controller
No dependencies exist between parameter data and process data.
Parameter data: approx. 5 ms (typical value)
For parameters concerning the motor control (e.g. C011), the processing time may be longer
(up to 30 ms).
Process data: 1 ms
Monitoring protocols Heartbeat (heartbeat producer and heartbeat consumer)
"BaseLine C" version:
1 Heartbeat Producer can be monitored.
"StateLine" version:
Up to 7 Heartbeat Producers can be monitored.
"HighLine" version:
Up to 15 Heartbeat Producers can be monitored.
Emergency telegram (to master)
Protocols