4 Device control (DCTRL)
4.1 Device commands
50
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.1.4 Import EPM data
The C002/12 = "1: On / start" device command activates the automatic import of parameters from
the memory module after the error message "PS04: Par.set incompatible".
4.1.5 Enable/Inhibit controller
The C002/16 = "1: On / start" device command enables the controller, provided that no other source
of a controller inhibit is active.
The C002/16
= "0: : On / start" device command enables the controller, provided that no other sour-
ce of a controller inhibit is active.
The motor becomes torqueless and coasts down.
When the controller is inhibited, the status output bCInhActive of the LS_DriveInterface
system
block is set to TRUE.
When the controller inhibit request is reset, the drive synchronises to the actual speed. For this
purpose,
If the flying restart circuit is activated in C990
, the flying restart function parameterised in
C991
is used for the synchronisation to the rotary or standing drive. Flying restart function
( 94)
Tip!
The controller can also be enabled or inhibited via the and toolbar icons.
C158
provides a bit coded representation of all active sources/triggers of a controller in-
hibit.
4.1.6 Activate/Deactivate quick stop
The C002/17 = "1: On / start" device command activates the quick stop function, i.e. the motor con-
trol is separated from the setpoint selection, and within the deceleration time parameterised in
C105
the motor is brought to a standstill (n
act
=0).
A pulse inhibit (CINH) is set if the "Auto-DCB" function has been activated via C019
.
The C002/17
= "0: Off / ready" device command deactivates the quick stop again, provided that no
other source of a quick stop is active.
Tip!
C159
provides a bit coded representation of all active sources/triggers of a quick stop.
Parameter Info Lenze setting
Value Unit
C105 Deceleration time - quick stop 2.000 s