Wiring the standard device
Control connections
Important notes
5
5.9
5.9.1
5.9-2
EDSVF9333V EN 3.0-06/2005
1
2
0
9300vec129
Fig. 5.9-1 Connection of cable shield to shield sheet
Shield sheet
Fasten shield sheet with M4 × 10 mm screw at the bottom of the control
card
Securely clamp cable shield with lugs
Stop!
ƒ Terminal strips must only be connected or disconnected when
no voltage is applied!
ƒ Wire the terminal strips before connecting them!
ƒ Unused terminal strips must also be plugged on to protect the
contacts.
Cable type Wire end ferrule Maximum cable
cross-section
Tightening
torque
Stripping
length
Rigid 2.5 mm
2
(AWG 14)
0.5 ... 0.6 Nm
(4.4 ... 5.3 lb-in)
5mm
Flexible
Without wire end
ferrule
2.5 mm
2
(AWG 14)
Flexible
Wire end ferrule
without plastic
sleeve
2.5 mm
2
(AWG 14)
Flexible
Wire end ferrule
with plastic sleeve
2.5 mm
2
(AWG 14)
Shield sheet installation
Terminal data