Commissioning
Operating mode
Vector control
6
6.8
6.8.2
6.8-9
EDSVF9333V EN 3.0-06/2005
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0087
Mot speed Æ 50 {1 rpm} 36000 Rated motor speed
Æ depending on C0086
z Motor selection in C0086 set
the corresponding rated motor
speed in C0087
z Change of C0087 sets
C0086 = 0
6.6-1
C0088
MOT CURRENT Æ 0.5 {0.1 A} 500.0 Rated motor current
Æ Depending on C0086
z Selection of a motor in C0086
sets the corresponding rated
motor current in C0088
z Change of C0088 sets
C0086 = 0
6.6-1
C0089
Mot frequency Æ 10 {1 Hz} 5000 Rated motor frequency
Æ depending on C0086
z Motor selection in C0086 sets
the corresponding rated motor
frequency in C0089
z Change of C0089 sets
C0086 = 0
6.6-1
C0090
Mot voltage Æ 0 {1 V} 1000 Rated motor voltage
Æ depending on C0086
z Motor selection in C0086 sets
the corresponding rated motor
voltage in C0090
z Change of C0090 sets C0086 =
0
6.6-1
C0091
Mot cos phi Æ 0.50 {0.01 } 1.00 Motor cos ϕ
Æ depending on C0086
z Motor selection in C0086 sets
the corresponding motor cos ϕ
in C0091
z Change of C0091 sets
C0086 = 0
6.6-1
C0092
Mot Ls Æ 0.0 {0.1 mH} 6500.0 Motor stator inductance
Æ Value is evaluated by motor
parameter identification from
C0088, C0089, C0090 and
C0091
Æ Selection of a motor in C0086
sets the corresponding stator
inductance value in C0092
6.6-1
C0148
ident run 0
0 WRK
stop
Ready
Motor data identification
1. Inhibit controller, wait until
drive has stopped
2. Enter the correct values of the
motor nameplate into C0087,
C0088, C0089, C0090, C0091
3. Set C0148 = 1, confirm with
4. Enable controller
The identification
–starts, goes off. The
motor ”whistles” but does
not rotate!
lastsapprox.1...2min
is completed when is lit
again
5. Inhibit controller:
6.6-13
1 WRK
run
Start identification