Commissioning
Adjusting the motor
Motor temperature monitoring with PTC or thermal contact
6
6.6
6.6.3
6.6-9
EDSVF9333V EN 3.0-06/2005
Codes for parameter setting
Code Possible settings IMPORTANT
No. Name Lenze Selection
C0585 MONIT OH8 3
0 TRIP
Configuration of motor
temperature monitoring
z Temperature monitoring via
PTC input (T1, T2)
6.6-8
See System
Manual
(extension)
2 Warning
3 Off
Note!
ƒ In the Lenze setting, the motor temperature monitoring is
switched off!
ƒ If you work with several parameter sets, the monitoring must
be activated separately in each parameter set!
1. Connecting the monitoring circuit of the motor to T1 and T2.
–With1.6kΩ <R<4kΩ, monitoring is activated.
2. Setting the controller reaction:
C0585 = 3: Temperature monitoring of the motor is switched off.
C0585 = 0: TRIP error message (display of keypad: OH8 )
C0585 = 2: Warning signal (display of keypad: OH8 )
Connect the PTC input with a fixed resistor:
ƒR>4kΩ: ThefaultmessageOH8mustbeactivated.
ƒR<1kΩ: Fault m essage must not be activated.