Wiring the standard device
Control connections
Without ”safe standstill” function
5
5.9
5.9.3
5.9-7
EDSVF9333V EN 3.0-06/2005
Supply via external voltage source
GND2 +24V+5 V
E5
A2 A3 A4 ST1
ST2
59
39
3k
47k
50mA
50mA
50mA
50mA
X5
28
E1 E2 E3 E4
3k
3k
3k
3k
3k
DC 24 V
(+18 V +30 V)
X11
K31K32 33 34
S1
+
K
SR
+
A1
X3
GND1 GND1
X6
1
AIN1 AIN2 AOUT1 AOUT2
2
3
4
AOUTx AOUTx
1
3
24
10k 10k
7762
63
242R
1
2
3
4
5
6
100k
100k
100k
100k
3.3nF
9300vec138
Fig. 5.9-5 Wiring of digital and analog inputs/outputs without ”safe standstill” function
with external voltage source
S1 Enable controller
The min. wiring requirements for operation
Note!
Supplying the digital inputs via an external voltage source
enables a backup operation in case of mains failure.After
switching off the mains voltage all actual values are continued
to be detected and processed.
ƒ Connectthepositivepoleoftheexternalvoltagesourcewith
X5/59 to establish the backup operation in the event of mains
failure.
ƒ The external voltage source must be able to supply a current
1A.
ƒ The starting current of the external voltage source is not
limited by the controller. Lenze recommends the use of
voltage sources with current limitation or with an internal
impedance of Z > 1 Ω.