Wiring the standard device
Basic devices in the power range 0.37 ... 11 kW
Mains connection, DC supply
5
5.4
5.4.3
5.4-5
EDSVF9333V EN 3.0-06/2005
L1 L2 L3
+UG -UG
PE
L1, L2, L3
+U , -U
GG
0.5...0.6 Nm
4.4...5.3 lb-in
2
0
1
9300std033
Fig. 5.4-3 Mains connection, DC supply for drive controllers 0.37 ... 11 kW
Mains cable
Shield sheet
Securely clamp mains cable shield w ith the lugs
Mains and DC bus connection
L1, L2, L3: Connection of mains cable
+U
G
,-U
G
: Connection of cable for devices in DC-bus connection
Cable cross-sections up to 4 mm
2
: Use wire end ferrules for flexible cables
Cablecross-sections>4mm
2
: Use pin-end connectors