Wiring the standard device
Basics for wiring according to EMC
Control cables
5
5.2
5.2.4
5.2-3
EDSVF9333V EN 3.0-06/2005
5.2.4 Control cables
ƒ Control cables must be shielded to minimise interference injections.
ƒ For lengths of 200 mm and more, use only shielded cables for analog
and digital inputs and outputs. U nder 200 mm, unshielded but twisted
cables may be used.
ƒ Place the shield correctly:
The shield connections of the control cables must be at a distance of
at least 50 mm from the shield connections of the motor cables and
DC cables.
For cables for digital inputs and outputs, place the shield at both
ends.
For cables for analog inputs and outputs, place the shield at one end
on the drive controller.
ƒ To achieve an optimum shielding effect (in case of very long cables,
with high interference) one shield end can be connected to PE potential
via a capacitor (e.g. 10 nF/250 V) (see sketch).
Fig. 5.2-2 Shielding of long, analog control cables