EasyManua.ls Logo

Lenze EVF9324

Lenze EVF9324
459 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting and fault elimination
Troubleshooting
Error analysis with the history buffer
9
9.2
9.2.2
9.2-2
EDSVF9333V EN 3.0-06/2005
Structure of the history buffer
Code Memory unit Entry Note
C0168/1 C0169/1 C0170/1 Memory unit 1 Active fault
If the fault is not available anymore or has
been acknowledged:
z The contents of the memory locations 1 ... 7
are moved one memory location ”higher”.
z The contents of memory location 8 is
deleted from the history buffer and cannot
be retrieved anymore.
z Memory location 1 is deleted (= no active
fault).
C0168/2 C0169/2 C0170/2 Memory unit 2 Last fault
C0168/3 C0169/3 C0170/3 Memory unit 3 Second to last fault
C0168/4 C0169/4 C0170/4 Memory unit 4 Third last fault
C0168/5 C0169/5 C0170/5 Memory unit 5 Fourth-last fault
C0168/6 C0169/6 C0170/6 Memory unit 6 Fifth-last fault
C0168/7 C0169/7 C0170/7 Memory unit 7 Sixth-last fault
C0168/8 C0169/8 C0170/8 Memory unit 8 Last but six fault
Explanations regarding the codes
C0168 Fault recognition and response to the reaction
z The entry is done as a LECOM error number
z If several fault with different reactions occur at the same time:
Only the fault is entered the reaction of which has the highest priority
(1.TRIP,2.message,3.warning).
z If faults with the same reactions occur (e.g. 2 messages):
Only the fault which occurred first is entered.
C0169 Time of the fault
z Reference time is the status of the power-on time meter (C0179).
z If a fault is immediately f ollowed by another fault for several times, only
thetimeofthelastoccurrenceisstored.
C0170 Frequency of the fault
z Thetimeofthelastoccurrenceisstored.
Set C0167 = 1 to delete the history buffer.
Delete history buffer

Table of Contents

Related product manuals